ME 26 PT100 or ME 26 PT1000
ANALOGIC OUTPUT FOR PT100 or PT1000 PLATINUM PROBE
![]() |
Zero adjustment |
|
||||||||||||
| Span adjustment | ||||||||||||||
| Calibration | ||||||||||||||
| Scale adjustment | ||||||||||||||
|
Compatible with : - 2680C multi-channels instrument, - ME52 rail DIN mono-channel - ME261B IP65 multi-channels. |
||||||||||||||
APPLICATION AND CONNECTION

TECHNICAL FEATURES
| ME
26 PT 100 For RTD 100 Ohm 2, 3 ou 4 wires Probe ME 26 PT 1000 For RTD 1000 Ohm 2, 3 or 4 wires Probe |
|
| 2 available ranges | -200°C/+200°C -200/+800°C , other ranges on request |
| Zero and Gain | Adjustable by trimmer (Adjustment in our laboratory) |
| Calibration by pushing switch | = 100 °C |
| Current in the probe | 1mA maximum. |
| Conditioning | Linearized |
| Linearity | 1. 10-3 for
-200/+200°C and 5. 10-3 for -200/+800°C |
| Output signal | ± 10V or 0 - 20 mA or 4-20mA |
| Output voltage bandwidth | 1KHz (other value on request) |
| Protection | Against short circuits |
| Power supply | 24 VDC ± 2V / 50 mA |
| Option: ME26ISO | 500V of insulation between the input and the output by extension board. |
| Option: RAL26EU | 100 x 160 mm Europe adapter DIN 41612 connector |